Industrial PC | Parameter setting & configuration

Parameter reference

Industrial PC extension modules

194

L

2.5 EN - 01/2012

C1582/1

C1582/2

C1582/3

C1586/2

C1586/3

C1586/4

Parameter | Name:

C1582/1 | ECAT DC: State

Data type: BITFIELD_3

Index: 22993.1

d

=

0x59D1.0x01

h

Display of the state of the distributed clocks

The bits are set to value 1 if the respective states are reached.
Value is bit-coded:

Bit 0 DC: Activated
Bit 1 DC: Sychronised
Bit 2 DC: Busy

;

Read access … Write access … CINH … PLC STOP … No transfer

Parameter | Name:

C1582/2 | ECAT DC: Perm. dev. slave sync

Data type: UNSIGNED_32

Index: 22993.2

d

=

0x59D1.0x02

h

Permissible deviation of the distributed clocks of all devices in nanoseconds. If the permissible deviation is

exceeded, the master will initiate a resynchronisation of the distributed clocks.
Display range

(min. value | unit | max. value)

0

ns

4294967295

;

Read access … Write access … CINH … PLC STOP … No transfer

Parameter | Name:

C1582/3 | ECAT DC: Current deviation

Data type: INTEGER_32

Index: 22993.3

d

=

0x59D1.0x03

h

Current maximum deviation of the distributed clocks of all devices in nanoseconds.
Display range

(min. value | unit | max. value)

0

ns

2147483647

;

Read access … Write access … CINH … PLC STOP … No transfer

Parameter | Name:

C1586/2 | ECAT config.: Checksum CRC-32

Data type: UNSIGNED_32

Index: 22989.2

d

=

0x59CD.0x02

h

Checksum of the master configuration file (loaded/activated by the stack). The stack determines the checksum of

the loaded/active master configuration file. If this file is not available, the value "0x00000000" will be displayed.

;

Read access … Write access … CINH … PLC STOP … No transfer

Parameter | Name:

C1586/3 | ECAT bus: Numb. slaves

Data type: UNSIGNED_32

Index: 22989.3

d

=

0x59CD.0x03

h

Number of slaves connected to the fieldbus
Display range

(min. value | unit | max. value)

0

4294967295

;

Read access … Write access … CINH … PLC STOP … No transfer

Parameter | Name:

C1586/4 | ECAT bus: Numb. slaves with DC

Data type: UNSIGNED_32

Index: 22989.4

d

=

0x59CD.0x04

h

Number of slaves connected to the fieldbus and supported by distributed clocks
Display range

(min. value | unit | max. value)

0

4294967295

;

Read access … Write access … CINH … PLC STOP … No transfer