Industrial pc | parameter setting & configuration – Lenze PC-based Automation Industrial PC User Manual

Page 180

Advertising
background image

Industrial PC | Parameter setting & configuration

Parameter reference

Industrial PC extension modules

180

L

2.5 EN - 01/2012

C1086/14

C1095/1

C1095/2

C1096/1

Parameter | Name:

C1086/14 | ECAT: Reset individual counters

Data type: UNSIGNED_32

Index: 23489.14

d

=

0x5BC1.0x0E

h

Reset frame and datagram counters (C1086/7 ... 13)
Selection list

(Lenze setting printed in bold)

0 No action
1 Reset - All counters
2 Reset - Tx frame counters
4 Reset - Rx frame counters
8 Reset - Lost frame counters

16 Reset - Cyclic frame counters
32 Reset - Cyclic datagram counters
64 Reset - Acyclic frame counters

128 Reset - Acyclic datagram counters

;

Read access ; Write access … CINH … PLC STOP ; No transfer

Parameter | Name:

C1095/1 | ECAT: Slave addressing mode

Data type: UNSIGNED_8

Index: 23480.1

d

=

0x5BB8.0x01

h

The addressing mode refers to the slave address (

C1095/2

).

Selection list

(Lenze setting printed in bold)

0 Position addressing

Auto increment addresses:

The addresses depend on the position of the respective

slave in the EtherCAT bus (i.e. 0, -1, -2, ...).

1 Node addressing

Physical addresses:

The addresses are assigned consecutively by the

»PLC Designer« (i.e. 1001, 1002, ...)

;

Read access ; Write access … CINH … PLC STOP ; No transfer

Parameter | Name:

C1095/2 | ECAT: Slave address

Data type: INTEGER_32

Index: 23480.2

d

=

0x5BB8.0x02

h

Use this code to select a slave whose parameters are to be displayed.

The addressing mode is specified in code

C1095/1

. A maximum of 4096 slaves can be addressed after the master.

Setting range

(min. value | unit | max. value)

Lenze setting

-65536

65536 0

;

Read access ; Write access … CINH … PLC STOP … No transfer

Parameter | Name:

C1096/1 | ECAT: Valid entry

Data type: UNSIGNED_8

Index: 23479.1

d

=

0x5BB7.0x01

h

This code indicates whether the entries/values of the following subcodes C1096/2 ... /38 are valid or not.

• Value "0": Invalid entry/value

• Value "1": Valid entry/value (The parameters of an available slave are displayed.)
Display range

(min. value | unit | max. value)

0

1

;

Read access … Write access … CINH … PLC STOP … No transfer