Table 10, Parameters for the open command – Vaisala Hydromet Data Collection Platform User Manual

Page 113

Advertising
background image

Chapter 3 _____________________________________________ Configuring Modules and Sensors

VAISALA______________________________________________________________________ 111

In order to have access to the sensor interface, the serial line parameters
have to be set to match those on the sensor. The easiest way to do this
is to create a setup with Lizard Setup Software. Select the correct
interface modules and parameters and run the setup.

Once the serial line parameters are correct, a pass-through access to the
connected sensors is allowed. You can open it from the QML logger
command shell by issuing the open command with the parameters
presented in

Table 10 on page 111

.

NOTE

When a separate service interface, usually RS-232, is available in the
sensor, it is recommended that you use it for the initial configuration.

The 2-wire RS-485 which operates in half duplex does not always
provide problem-free access to service connection. Also, note that
keystrokes are not echoed by the sensor.

Table 10

Parameters for the Open Command

Connector in Lizard

Parameter

Alias

COM0

COM0

COM0

COM1

COM1

COM1

DMX501 (MOD1/1)

DMX501_0

MOD1

DMX501 (MOD2/1)

DMX501_1

MOD2

DSI485A (MOD1/1)

DSI485_0

MOD1

DSI485A (MOD2/1)

DSI485_1

MOD2

DSI486 (MOD1/1)

DSI485_0_0

MOD1_2

DSI486 (MOD1/2)

DSI486_0_1

1

1. With the dual RS-485 module, the RS-232 connection is possible only to

the channel B on the module, and thus the last number is 1.

MOD1_1

DSI486 (MOD2/1)

DSI486_1_0

MOD2_2

DSI486 (MOD2/2)

DSI486_1_1

1

MOD2_1

DSI486SDI (MOD1/3)

DSI486SDI_0

MOD1_3

DSI486SDI (MOD2/3)

DSI486SDI_1

MOD2_3

DSU232 (MOD1/1)

DSU232_0_0

2

2. With the RS-232 and dual RS-485 modules, the number between the

underline characters stands for the module place, that is, MOD1 or MOD2,
and the last number for the channel on that particular module.

MOD1_1

DSU232 (MOD1/2)

DSU232_0_1

MOD1_2

DSU232 (MOD2/1)

DSU232_1_0

MOD2_1

DSU232 (MOD2/2)

DSU232_1_1

MOD2_2

DSU232SDI (MOD1/3)

DSU232SDI_0

MOD1_3

DSU232SDI (MOD2/3)

DSU232SDI_1

MOD2_3

Advertising