Figure 15 – Vaisala Hydromet Data Collection Platform User Manual

Page 53

Advertising
background image

Chapter 3 _____________________________________________ Configuring Modules and Sensors

VAISALA_______________________________________________________________________ 51

In the example in

Figure 14 on page 50

, the configuration is as follows:

-

Test output 0 toggles between on and off in a one-minute cycle.

-

Test output 3 is on for one minute before each full hour.

Alternatively, you can control the outputs with alarms, for example, by
activating the output signal when the alarm condition is met.

0711-113

Figure 15

Alarms View: Controlling Digital Output Using an
Alarm

In the example, the configuration activates output 2 when the air
temperature measured by the QMH101 sensor rises above +15 °C.

Configure the alarm condition in the Alarms view; see

Figure 15 on

page 51

for an example.

The inputs of the digital I/O module can be used like any other
application variables, that is, for the following:

-

Reporting

-

Logging

-

As an alarm input