User's Guide ______________________________________________________________________

312 _________________________________________________________________ M210933EN-C

3.

In the IP Services view, add and configure a virtual COM port for
report transmission to the data acquisition system.

a.

Remove the selection from the Enable Telnet protocol
option.

b.

Set the value of the Inactivity timeout parameter to 10
seconds.

c.

Enable the active connection by selecting the Active
Connection
, With any character option. When this option is
selected for the virtual COM port with default parameters, a
dialog for configuring remote hosts is displayed
automatically; see

Figure 151 on page 312

.

0710-117

Figure 151

Configuring Remote Hosts for Virtual COM
Ports

With this configuration, the virtual COM port will connect to the
configured remote system as soon as it receives application data to
be transmitted, that is, it begins to transmit a report. The connection
will be automatically closed 10 seconds after the data has been
sent.

NOTE

The values shown do not represent any existing server connection. In
order to have a functional system, the parameter values must be
changed either in the setup or by changing the values in the parameter
set VCOM0. The values of the parameter must represent the IP
address and port of the destination server.