SCPI Commands for Digital Interfaces

TM-XDOP-01XN

4–33

AC Off Protection

The user has the option of setting whether the AC Off protection mechanism is
latched or automatically resumes operation.

SENSE:VOLT:AC:PROT:LATCH {ON|1|OFF|0}

Where:

ON

or 1 means the supply will be latched in shut down if an AC Off condition

occurs, until the user re-enables the output.

and

OFF

or 0 means the supply will automatically resume operation when the AC line

input returns to normal.

The default value is OFF.

To query if AC Off has tripped:

SENSE:VOLT:AC:PROT:TRIP?

Clear Protection Event

To clear a protection mechanism that has tripped:

OUTP:PROT:CLE

This will clear all protection mechanisms and re-enable the output. If the
condition that caused the alarm still exists, the protection will be allowed to trip
again.

View Power Supply Output

The following 3 commands query the voltage, current, or power being supplied at
the output terminals.

To measure the voltage output:

MEAS:VOLT?

To measure the current output:

MEAS:CURR?

To measure the power output:

MEAS:POW?