Electrical Specifications—Summary

TM-XDOP-01XN

A–3

)

Table A-2 Specifications for 6000 Watt units (80V to 600V Models)

Models

80–75

100–60

150–40

300–20

600–10

Output Ratings:

Output Voltage

a

Output Current

b

Output Power

a.

Minimum output voltage is <0.3% of rated voltage at zero output setting.

b.

Minimum output current is <0.2% of rated current at zero output setting when measured with rated load resistance.

0–80 V
0–75 A
6000 W

0–100 V
0–60 A
6000 W

0–150 V
0–40 A
6000 W

0–300 V
0–20 A
6000 W

0–600 V
0–10 A
6000 W

Line Regulation:

c

Voltage

(0.01% of Vmax)

Current (0.05% of Imax)

c.

For input voltage variation over the AC input voltage range, with constant rated load.

8 mV
37.5 mA

10 mV
30 mA

15 mV
20 mA

30 mV
10 mA

60 mV
5 mA

Load Regulation:

d

Voltage (0.05% of Vmax + 5 mV)
Current (0.1% of Imax + 20 mA)

d.

For 0–100% load variation, with constant nominal line voltage.

45 mV
95 mA

55 mV
80 mA

80 mV
60 mA

155 mV
40 mA

305 mV
30 mA

Meter Accuracy:

Voltage (0.15% of Vmax)
Current (0.5% of Imax)

120 mV
375 mA

150 mV
300 mA

225 mV
200 mA

450 mV
100 mA

900 mV
50 mA

Output Noise (0–20 MHz):

Voltage (p–p)

100 mV

100 mV

150 mV

250 mV

350 mV

Output Ripple (rms):

Voltage
Current

e

e.

Current mode noise is measured from 10% to 100% of rated output voltage, full current, unit in CC mode.

15 mV
320 mA

20 mV
230 mA

20 mV
120 mA

30 mV
50 mA

80 mV
25 mA

OVP Adjustment Range:

(0% to 103% of Vmax)

0–82.4 V

0–103 V

0–154.5 V 0–309 V

0–618 V

Efficiency:

f

f.

Typical efficiency at nominal input voltage and full output power.

0.89

0.90

0.90

0.91

0.91

Drift (30 minutes):

g

Voltage (0.04% of Vmax)
Current (0.6% of Imax)

g.

Maximum drift over 30 minutes with constant line, load, and temperature, after power on.

32 mV
450 mA

40 mV
360 mA

60 mV
240 mA

120 mV
120 mA

240 mV
60 mA

Drift (8 hours):

h

Voltage (0.02% of Vmax)
Current (0.04% of Imax)

h.

Maximum drift over 8 hours with constant line, load, and temperature, after 30 minute warm-up.

16 mV
30 mA

20 mV
24 mA

30 mV
16 mA

60 mV
8 mA

120 mV
4 mA

Temperature Coefficient:

i

Voltage (0.04% of Vmax/°C)
Current (0.06% of Imax/°C)

i.

Change in output per

°C change in ambient temperature, with constant line and load.

32 mV
45 mA

40 mV
36 mA

60 mV
24 mA

120 mV
12 mA

240 mV
6 mA