Installation

2–8

TM-XDOP-01XN

AC Input Wire

The manufacturer recommends the AC input wire specified in Table 2-2 and Table
2-3. This must be permanently connected to an approved AC distribution box with
suitably rated over-current protection. If you require a special cord, contact the
manufacturer.

f

Table 2-2 AC Wire Specification for 6000 Watt Units

AC Input Voltage Range

Wire

190–242Vac, 47–63Hz,
3-phase, 4 wire (standard)

4 x 10 AWG (3 wire plus safety ground), stranded
copper, 60

°

C minimum, 300V, 0.800 in.

maximum cable diameter, rated for 25A.

342–500Vac, 47–63Hz,
3-phase, 4 wire (HV-Input)

4 x 14 AWG (3 wire plus safety ground), stranded
copper, 60

°

C minimum, 600V, 0.800 in.

maximum cable diameter, rated for 13A.

Table 2-3 AC Wire Specification for 12000 Watt Units

AC Input Voltage Range

Wire

190–242Vac, 47–63Hz,
3-phase, 4 wire (standard)

4 x 6 AWG (3 wire plus safety ground), stranded
copper, 60

°

C minimum, 300V, outside diameter

(OD) of cable is

≤ 1 in., rated for 50 A.

342–500Vac, 47–63Hz,
3-phase, 4 wire (HV-Input)

4 x 10 AWG (3 wire plus safety ground), stranded
copper, 60

°

C minimum, 600V, outside diameter

(OD) of cable is

≤ 1 in., rated for 25 A.