Xantrex Technology XDC 20-600 User Manual

Page 175

Advertising
background image

SCPI Commands for Digital Interfaces

TM-XDOP-01XN

4–61

Power-on Status Clear

The Power-On Status Clear command controls the automatic power-on clearing of
the Service Request Enable Register, the Standard Event Status Enable Register,
the Parallel Poll Enable Register and the Error/Event Queue.

Command:

*PSC {0|1}, *PSC?

SCPI equivalent for multichannel use:

SYSTem[<channel>]:POSClear {ON|OFF|0|1}

SYSTem[<channel>]:POSClear?

Individual Status Query

The individual status query allows the programmer to read the state of the IEEE
488.1 ist (individual status) message without performing a parallel poll. The query
returns a "1" or "0."

The ist message is formed by ANDing the bits in the Parallel Poll Enable Register
(*PRE) with the Status Byte and then ORing the result. In other words, the ist is
TRUE if any of bits of the Parallel Poll Enable Register ANDed with the Status
Byte are TRUE.

Command:

*IST?

Operation Complete

The Operation Complete command causes the power supply to generate the
operation complete message in the Standard Event Status Register when all
pending operations have been finished.

Command:

*OPC, *OPC?

Wait-to-Continue Command

The Wait-to-Continue command prevents the power supply from executing any
further commands or queries until the no-operation-pending flag is TRUE.

Command:

*WAI

TM-XDOP-01XN.book Page 61 Monday, July 17, 2006 11:19 AM