Electrical Specifications—Summary

TM-XDOP-01XN

A–5

Table A-4 Specifications for 12000 Watt units (80V to 600V Models)

Models

80–150

100–120

150–80

300–40

600–20

Output Ratings:

Output Voltage

a

Output Current

b

Output Power

a.

Minimum output voltage is <0.3% of rated voltage at zero output setting.

b.

Minimum output current is <0.2% of rated current at zero output setting when measured with rated load resistance.

0–80 V
0–150 A
12000 W

0–100 V
0–120 A
12000 W

0–150 V
0–80 A
12000 W

0–300 V
0–40 A
12000 W

0–600 V
0–20 A
12000 W

Line Regulation:

c

Voltage

(0.01% of Vmax)

Current (0.1% of Imax)

c.

For input voltage variation over the AC input voltage range, with constant rated load.

8 mV
150 mA

10 mV
120 mA

15 mV
80 mA

30 mV
40 mA

60 mV
20 mA

Load Regulation:

d

Voltage (0.05% of Vmax + 5 mV)
Current (0.2% of Imax + 40 mA)

d.

For 0–100% load variation, with constant nominal line voltage.

45 mV
340 mA

55 mV
280 mA

80 mV
200 mA

155 mV
120 mA

305 mV
80 mA

Meter Accuracy:

Voltage (0.15% of Vmax)
Current (0.5% of Imax)

120 mV
750 mA

150 mV
600 mA

225 mV
400 mA

450 mV
200 mA

900 mV
100 mA

Output Noise (0–20 MHz):

Voltage (p–p)

100 mV

100 mV

150 mV

250 mV

350 mV

Output Ripple (rms):

Voltage
Current

e

e.

Current mode noise is measured from 10% to 100% of rated output voltage, full current, unit in CC mode.

15 mV
640 mA

20 mV
460 mA

20 mV
240 mA

30 mV
100 mA

80 mV
50 mA

OVP Adjustment Range:

(0% to 103% of Vmax)

0–82.4 V

0–103 V

0–154.5 V 0–309 V

0–618 V

Efficiency:

f

f.

Typical efficiency at nominal input voltage and full output power.

0.89

0.90

0.90

0.91

0.91

Drift (30 minutes):

g

Voltage (0.04% of Vmax)
Current (0.6% of Imax)

g.

Maximum drift over 30 minutes with constant line, load, and temperature, after power on.

32 mV
900 mA

40 mV
720 mA

60 mV
480 mA

120 mV
240 mA

240 mV
120 mA

Drift (8 hours):

h

Voltage (0.02% of Vmax)
Current (0.05% of Imax)

i

h.

Maximum drift over 8 hours with constant line, load, and temperature, after 30 minute warm-up.

i.

Current drift for 600V-20A unit is 0.08% of Imax.

16 mV
75 mA

20 mV
60 mA

30 mV
40 mA

60 mV
20 mA

120 mV
16 mA

Temperature Coefficient:

j

Voltage (0.04% of Vmax/°C)
Current (0.06% of Imax/°C)

j.

Change in output per

°C change in ambient temperature, with constant line and load.

32 mV
90 mA

40 mV
72 mA

60 mV
48 mA

120 mV
24 mA

240 mV
12 mA