Electrical installation, Avertissement – Lenze 8400 User Manual

Page 165

Advertising
background image

Electrical installation

Safety instructions for the installation according to U

L

or U

R

6

165

EDS84ASC552 EN 9.1

The values of the fuses used may be equal to or fall below the values in the following table:

Branch circuit protection

Fuse [A]

Circuit breaker

Type

with mains

choke

without mains

choke

Type 5kA rms

Type 50kA rms

Rating

E84AVxxx2512

6

6

Schneider Electric:

Multi9 C60

Charact. C

Moeller:

FAZ-C

Charact. C

Siemens:

3RV1742

15 A

E84AVxxx3712

10

10

15 A

E84AVxxx5512

10

10

15 A

E84AVxxx7512

15

15

15 A

E84AVxxx1122

20

20

20 A

E84AVxxx1522

25

25

25 A

E84AVxxx2222

30

30

30 A

E84AVxxx3714

6

6

15 A

E84AVxxx5514

6

6

15 A

E84AVxxx7514

6

6

15 A

E84AVxxx1124

10

10

15 A

E84AVxxx1524

10

10

15 A

E84AVxxx2224

10

10

15 A

E84AVxxx3024xxS

15

15

15 A

E84AVxxx3024xx0

15

15

15 A

E84AVxxx4024

20

20

20 A

E84AVxxx5524

20

20

20 A

E84AVxxx7524

20

25

Siemens:

3RV1742

25 A

E84AVxxx1134

30

40

40 A

E84AVxxx1534

50

-

50 A

E84AVxxx1834

60

60

-

-

-

E84AVxxx2234

60

-

-

E84AVxxx3034

80

-

-

-

-

E84AVxxx3734

100

-

-

-

-

E84AVxxx4534

125

-

-

-

-

Avertissement !

Pour obtenir la certification CSA, les entraînements doivent être destinés à une

utilisation avec des selfs homologuées UL (XPTQ2/8, FOKY2/8) ou certifiées

CSA (XPTQ2, FOKY2), n° de dossier E103521 ou E198787, montées côté

alimentation des équipements.
Ces selfs sont répertoriées sous les 4.2 Caractéristiques assignées ainsi qu’au

chapitre 11.2 Accessoires.