Electrical installation, Stateline: stripping dimensions, Highline: stripping dimensions – Lenze 8400 User Manual

Page 211: Topline: stripping lengths

Advertising
background image

Electrical installation

Common control terminals

Important notes

6

211

EDS84ASC552 EN 9.1

Strip cables
According to the selected lock-in position of the shield sheet, strip the control cables. For

this, strip the cable ends and the cable sheath at the shield lug.
The following table shows the stripping length for the control cables depending on the

selected lock-in position of the shield sheet.

X1

X3, X107

X4, X5

;

;

84MOTL001_e

84MOTL001_d

84MOTL001_f

ƒ

StateLine: stripping dimensions

X1

X3

X4

min.

max.

min.

max.

a

[mm]

a

[mm]

[mm

2

]

[AWG]

a

[mm]

a

[mm]

[mm

2

]

[AWG]

[mm

2

]

[AWG]

110

135

0.2 ... 1.5

24 ... 16

150

175

0.2 ... 1.5

24 ... 16

0.2 ... 1.5

24 ... 16

ƒ

HighLine: stripping dimensions

X1

X3

X4, X5

X107

min.

max.

min.

max.

min.

max.

a

[mm]

a

[mm]

[mm

2

]

[AWG]

a

[mm]

a

[mm]

[mm

2

]

[AWG]

[mm

2

]

[AWG]

a

[mm]

a

[mm]

[mm

2

]

[AWG]

110

135

0.2 ... 1.5

24 ... 16

150

175

0.2 ... 1.5

24 ... 16

0.2 ... 1.5

24 ... 16

115

140

0.2 ... 1.5

24 ... 16

ƒ

TopLine: Stripping lengths

X1

X3/X5

X4/X107

min.

max.

min.

max.

min.

max.

a

a

a

a

a

a

[mm]

[mm]

[mm

2

]

[AWG]

[mm]

[mm]

[mm

2

]

[AWG]

[mm]

[mm]

[mm

2

]

[AWG]

110

135

0.2 ... 1.5

24 ... 16

150

175

0.2 ... 1.5

24 ... 16

115

140

0.2 ... 1.5

24 ... 16

Note!

Devices including safety engineering have an increased stripping length ”a”:

ƒ

by 10 mm when the shield sheet is pulled out to its minimum length

ƒ

by 15 mm when the shield sheet is pulled out to its maximum length