Technical data

Rated data

Operation with increased power at a 500 V mains

4

65

EDS84ASC552 EN 9.1

Fuses and cable cross-sections

Operation without external mains choke/mains filter
Type

Installation according to EN 60204-1

1)

Installation according

to UL

2)

FI

3)

L1, L2, L3 - Laying system

L1, L2, L3

B2

C

F

[A]

[A]

[mm

2

]

[mm

2

]

[mm

2

]

[A]

[AWG]

[mA]

E84AVxxx3714

C 6

6

1.0

-

-

6

18

 30

3)

E84AVxxx5514

C 6

6

1.0

-

-

6

18

E84AVxxx7514

-

-

-

-

-

-

-

-

E84AVxxx1124

C 10

10

1.5

-

-

10

16

 30

3)

E84AVxxx1524

C10

10

1.5

-

-

10

16

E84AVxxx2224

-

-

-

-

-

-

-

-

E84AVxxx3024xxS

-

-

-

-

-

-

-

-

E84AVxxx3024xx0 C 16

16

2.5

-

-

15

14

 300

3)

E84AVxxx4024

C 16

16

2.5

-

-

20

12

E84AVxxx5524

-

-

-

-

-

-

-

-

E84AVxxx7524

C 32

32

10

-

-

25

10

 300

3)

E84AVxxx1134

-

-

-

-

-

-

-

-

E84AVxxx1534

-

-

-

-

-

-

-

-

E84AVxxx1834

-

-

-

-

-

-

-

-

E84AVxxx2234

-

-

-

-

-

-

-

-

E84AVxxx3034

-

-

-

-

-

-

-

-

E84AVxxx3734

-

-

-

-

-

-

-

-

E84AVxxx4534

-

-

-

-

-

-

-

-

1)

These values are recommendations only. Other dimensioning values/laying systems are possible (e.g. according to

VDE 0298-4). The cable cross-sections apply under the following conditions: Use of PVC-insulated copper cables,

conductor temperature < 70 °C, ambient temperature < 45°C, no bundling of cables or cores, three loaded cores.

2)

Use UL-approved cables, fuses and fuse holders only.

UL fuse: voltage  500 V, tripping characteristic for example ”H”, ”K5” or ”CC”. The cable cross-sections apply under

the following conditions: conductor temperature < 75 °C, ambient temperature < 45°C.

3)

Universal-current sensitive earth-leakage circuit breaker, short-time delay

If cables are longer than 50 m, the protective circuit-breaker may respond, depending on the cable type and

switching frequency.

Circuit breaker

Fuse of gG/gL utilisation category or semiconductor fuses of gRL utilisation category

Fuse

Observe national and regional regulations