Electrical installation

Devices in a power range of 30 ... 45 kW (3/PE AC 400 V)

Terminal assignment of the power connections

6

208

EDS84ASC552 EN 9.1

Connection of external brake resistor

Terminal X105

Labelling

Description

Rb1, Rb2

Brake resistor

Functional earth

HF-shield termination by connection to PE

8400GG097b

Terminal data

PE

Conductor

cross-section

Tightening

torque

Conductor

cross-section

Tightening

torque

[mm

2

]

[AWG]

[Nm]

[lb-in]

[mm

2

]

[AWG]

[Nm]

[lb-in]

E84AVxxx3034

E84AVxxx3734

E84AVxxx4534

16 ... 50

6 ... 0

4.0

35

Inbus

SW 4

2.5 ... 25

12 ... 2

4.0

35

PZ 2

7 x 1

Please read the information on how to install and connect the brake resistor in

the corresponding mounting instructions.