Electrical installation, Stateline, highline – Lenze 8400 User Manual

Page 214

Advertising
background image

Electrical installation

Common control terminals

System bus connection (CANopen)

6

214

EDS84ASC552 EN 9.1

6.6.2.1

Wire CAN plug connector (X1) and ensure bus termination.

ƒ

Wire CAN plug connector (X1).
– Only install shielded bus cables to avoid interference injection.
– Fix the bus cable connected to plug connector X1 to the shield sheet of the

controller.

ƒ

Ensure bus termination.
– Only required if the controller is the first or the last node of the CAN bus.
– Activate the bus termination vis DIP switch ”R”.

Terminal data

Conductor cross-section

Tightening torque

[mm

2

]

[AWG]

[Nm]

[lb-in]

Flexible

0.2 ... 1.5

24 ... 16

-

-

-

With wire end ferrule

Specification of the bus cable
We recommend the use of CAN cables in accordance with ISO 11898-2:

CAN cable in accordance with ISO 11898-2
Cable type

Paired with shielding

Impedance

120  (95 ... 140 )

Cable resistance/cross-section

Cable length  300 m  70 m/m / 0.25 … 0.34 mm

2

(AWG22)

Cable length 301 … 1000 m  40 m/m / 0.5 mm

2

(AWG20)

Signal propagation delay

 5 ns/m

StateLine, HighLine

X1

CAN-Ground

X1

R

CL

C

H

120Ω

CG

CAN-Low

CAN-High

EDS84AVxxxx

,

"

"

"

CL

C

H

CG

d c

b a 6

4 32 16 8 4 2 1

Baud

CAN Adress

O

N

8400HLC048

8400SLC041

Fig. 6-29

CANopen connection