Electrical installation

Common control terminals

System bus connection (CANopen)

6

217

EDS84ASC552 EN 9.1

Segment cable length
2. Check whether the segment cable length is complied with.
The segment cable length is determined by the used cable cross-section and the number

of nodes. If no repeaters are used, the segment cable length corresponds to the total cable

length.

Maximum number

of nodes per

segment

Cable cross-section
0.25 mm

2

0.5 mm

2

0.75 mm

2

1.0 mm

2

2

240 m

430 m

650 m

940 m

5

230 m

420 m

640 m

920 m

10

230 m

410 m

620 m

900 m

20

210 m

390 m

580 m

850 m

32

200 m

360 m

550 m

800 m

63

170 m

310 m

470 m

690 m

Tab. 6-2

Segment cable length

3. Comparison of the two determined values.
If the value determined from Tab. 6-2 is lower than the total cable length to be

implemented from Tab. 6-1, repeaters must be used. Repeaters divide the total cable

length into segments.

Example: Selection help

Selections

Cable cross-section:

0.5 mm

2

(acc. to cable specification  214)

Number of nodes:

63

Repeater:

Lenze repeater, type 2176 (cable reduction: 30 m)

For a max. number of nodes (63), the following cable lengths / numbers of repeaters must

be complied with according to selection:

Baud rate [kbps]

10

20

50

125

250

500

800

1000

Max. cable length [m]

8075

4013

1575

600

275

113

38

13

Segment cable length [m]

270

270

270

270

270

113

38

13

Number of repeaters

30

15

6

2

1

-

-

Check the use of repeaters

Note!

The use of another repeater is recommended as

ƒ

Service interface

Advantage: Trouble-free connection to running bus operation is possible.

ƒ

Calibration interface

Advantage: The calibration / programming unit remains electrically

isolated.

Selections

Baud rate:

125 kbps

Cable cross-section:

0.5 mm

2

Number of nodes:

28

Cable length:

450 m