Safety engineering, Electrical installation, Hw revision: up to 1b – Lenze 8400 User Manual

Page 284: Hw revision: from 2a

Advertising
background image

Safety engineering

Electrical installation

10

284

EDS84ASC552 EN 9.1

HW revision: Up to 1B

X80

Labelling

Description

Electrical data

SIA

SI

B

GI

24O

DO1

GO

SIA

Safe input, channel A

SIA: I

typ

= 100 mA

GI

GND potential for SIA/SIB

LOW: -3 ... 5 V,

HIGH: 15 ... 30 V

SIB

Safe input, channel B

SIB: I

typ

= 28 mA

Supply through safely

separated power supply unit

(SELV/PELV)

GO

GND potential feedback

24 V, max. 0.7 A

short-circuit-proof

LOW-active

Supply through safely

separated power supply unit

(SELV/PELV)

24O

24 V voltage supply feedback

E84ABSB003

DO1

Non-safe signalling output: ”Safe pulse

inhibit”

HW revision: From 2A

X80

Labelling

Description

Electrical data

SIA

SI

B

GI

24O

DO1

GO

SIA

Safe input, channel A

SIA, SIB: I

typ

= 12 mA

LOW: -3 ... 5 V,

HIGH: 15 ... 30 V

Supply through safely

separated power supply unit

(SELV/PELV)

GI

GND potential for SIA/SIB

SIB

Safe input, channel B

GO

GND potential feedback

24 V, max. 0.7 A

short-circuit-proof

LOW-active

Supply through safely

separated power supply unit

(SELV/PELV)

24O

24 V voltage supply feedback

DO1

Non-safe signalling output: ”Safe pulse

inhibit”

E84ABSB003

Terminal data

Conductor cross-section

Tightening torque

[mm

2

]

[AWG]

[Nm]

[lb-in]

Rigid

0.14 ... 1.5

26 ... 16

Spring terminal

With wire end

ferrule

0.25 ... 0.5

24 ... 20