Electrical installation

Devices in the power range 0.37 ... 22 kW (3/PE AC 400 V)

Terminal assignment of the power connections

6

192

EDS84ASC552 EN 9.1

Connecting the controller to protective earth
Using the PE connection on the motor side the controller and the motor cable can be

connected to protective earth. Additional protective earthing of the controller can be

carried out via this connection in order to comply with the requirements regarding the

operation of devices with an increased discharge current to PE.
How to proceed:
1. Observe the above-mentioned steps regarding stripping and shielding.
2. Connect a second cable to the PE connection and earth it. ( 187).

;;

;;

;;

;

;

8400GG059

Fig. 6-19

Connecting controllers of device size 4 ... 6 to protective earth

Mains connection

Terminal X100

Labelling

Description

PE

L1

L2

L3

Connection of the mains phases L1, L2, L3

PE

Connection for the PE conductor

8400GGx001b

Terminal data

PE

Conductor

cross-section

Tightening

torque

Conductor

cross-section

Tightening

torque

[mm

2

]

[AWG]

[Nm]

[lb-in]

[mm

2

]

[AWG]

[Nm]

[lb-in]

E84AVxxx3714

E84AVxxx5514

E84AVxxx7514

E84AVxxx1124

E84AVxxx1524

E84AVxxx2224

E84AVxxx3024xxS

1 ... 2.5

18 ... 12

0.5

4.4

3.5 x 0.6

1 ... 6

18 ... 10

1.7

15

PZ 2

7 x 1

E84AVxxx3024xx0

E84AVxxx4024

E84AVxxx5524

1 ... 6

18 ... 10

0.5

4.4

3.5 x 0.6

2.5 ... 16

12 ... 6

3.4

30

PZ 2

7 x 1

E84AVxxx7524

E84AVxxx1134

E84AVxxx1534

1 ... 16

18 ... 6

1.2

10.6

5.5 x 1

2.5 ... 16

12 ... 6

3.4

30

PZ 2

7 x 1

E84AVxxx1834

E84AVxxx2234

1.5 ... 25

16 ... 2

3.5

31

6.5 x 1

2.5 ... 25

12 ... 2

4.0

35

PZ 2

7 x 1