Test steps

Cable length

See

1. Total cable length at 125 kbps:

600 m

From Tab. 6-1

2. Segment cable length for 28 nodes and a cable cross-section of

0.5 mm

2

:

360 m

From Tab. 6-2

3. Comparison: The value in point 2 is lower than the cable length of 450 m which must be implemented.

Result

ƒ

Use of repeaters
– Without the use of repeaters, a cable length of 450 m cannot be implemented.

After 360 m (point 2), a repeater must be used.

– The Lenze repeater, type 2176 is used (cable reduction: 30 m).

ƒ

Calculation of the max. cable length:
– First segment: 360 m
– Second segment: 360 m (acc. to Tab. 6-1)

minus

30 m (cable reduction if a repeater

is used)

– Max. cable length that can be implemented if a repeater is used: 690 m.

Hence, the selected cable length can be implemented.