Safety engineering, Technical data – Lenze 8400 User Manual

Page 281

Advertising
background image

Safety engineering

Technical data

10

281

EDS84ASC552 EN 9.1

HW revision: From 2A - detailed features of the inputs and outputs of the safety

system

Terminal

Specification

[Unit]

Min.

Typ.

Max.

SIA, SIB

Low signal

V

-3

0

5

High signal

V

15

24

30

Input capacitance at switch-off

nF

3

Switch-off time

(depends on the controller: Size 1 - 3)

ms

6

Switch-off time

(depends on the controller: From size 4)

ms

4

Running time

ms

1

Input current

mA

2

15

Input capacitance at switch-on

nF

100

Input delay (tolerated test pulse)

ms

1

Test pulses permissible at intervals of

ms

10

GI

Ground for SIA/SIB
When the polarity is reversed: No function, no

destruction

24O, GO

Supply voltage U

24O

for the output DO1 by a safely

separated power supply unit (SELV/PELV)

V

18

24

30

DO1

Low signal

V

0.8

High signal

V

U

24O

- 1 V

24O, GO, DO1

Output current

A

0.7

Safety-related parameters acc.to IEC 61508-1 to -7 and IEC 62061

Specification

Value

Comment

Safety Integrity Level

SIL 3

PFH [1/h]

9.05 E-10 0.9 % of SIL 3

PFD

7.92 E-5

7.9 % of SIL 3 after T = 20 years

Proof test interval

20 years

Mission time

Safety-related parameters acc. to EN ISO 13849-1

Specification

Value

Comment

Performance Level

e

Category

4

MTTF

d

High

68619 years

Diagnostic coverage DC

High

99 %