Technical data

Overcurrent operation

4

72

EDS84ASC552 EN 9.1

The curves of typical load functions and the simulation of the ”Ixt” function are shown in

the following illustration:

t

0

100%

1

0

2

I

[%]

aN8

T

2

T

3

T

4

T

1



‚

8400IZ180

Fig. 4-2

Overcurrent capacity in 230/400 V operation at 45° C

Pulse load (15 s cycle)

Calculation equation:

Peak current

A ⋅ T

1

+C ⋅ T

2

T

1

+T

2

≦ 100%

Unloading current

T

1

Peak current period

T

2

Unloading current period

Permanent load (180 s cycle)

Calculation equation:

Peak current

B ⋅ T

3

+C ⋅ T

4

T

3

+T

4

≦ 100%

Unloading current

T

3

Peak current period

T

4

Unloading current period

I

aNx

Rated value of continuous output

current

15-s cycle

f = 2 kHz

f = 4 kHz

f = 8 kHz

f = 16 kHz

I

amax

/I

aN8

[%]

200

75

200

75

200

75

133

50

180-s cycle

f = 2 kHz

f = 4 kHz

f = 8 kHz

f = 16 kHz

I

amax

/I

aN8

[%]

150

75

150

75

150

75

100

50

Tip!

For calculations of application-specific cycles please contact your Lenze contact

person.