Commissioning – Lenze 8400 User Manual

Page 243

Advertising
background image

Commissioning

Before switching on

7

243

EDS84ASC552 EN 9.1

Notes for motor operation

Danger!

ƒ

For thermal reasons, continuous operation of self-ventilated motors at low

field frequency and rated motor current is not permissible. If required,

activate a motor temperature monitoring with C00585

– motor temperature monitoring with I

2

xt (see software manual)

– motor temperature monitoring with motor PTC (see software manual).

ƒ

Select 87-Hz operation under code C00015 if an asynchronous motor in

delta connection (nameplate data: 400 V/230 V) is to be operated on a

frequency inverter for a supply voltage of 400 V.

Tip!

In the Lenze setting, the ”linear V/f characteristic” operating mode is set as

motor control. The parameter settings are preset so that if the frequency

inverter and the 50 Hz asynchronous machine match in terms of power, the

controller is ready for operation without any further need for parameterisation

and the motor operates satisfactorily.
Recommendations for the following application cases

ƒ

If the frequency inverter and the motor differ strongly in terms of

power
– Set code C00022 (I

max

limit in motor mode) to 2.0 I

N(motor)

.

ƒ

If a high starting torque is required
– When the motor is idling, set the code C00016 (V

min

boost) so that a

rated motor current flows with a field frequency f = 3 Hz (C00058).

ƒ

For noise reduction
– Set code C00018 to the value ”3” (switching frequency 16 kHz

sin var

).

ƒ

If a high torque without feedback is to be available at low speeds, we

recommend the ”vector control” mode.