Technical data, Rated data operation at rated mains voltage 230 v – Lenze 8400 User Manual

Page 38

Advertising
background image

Technical data

Rated data

Operation at rated mains voltage 230 V

4

38

EDS84ASC552 EN 9.1

Fuses and cable cross-sections

Operation without external mains choke/mains filter
Type

Installation according to EN 60204-1

1)

Installation according

to UL

2)

FI

3)

L1, N - laying system

L1, N

B2

C

F

[A]

[A]

[mm

2

]

[mm

2

]

[mm

2

]

[A]

[AWG]

[mA]

E84AVxxx2512

C 6

6

1

-

-

6

18

 30

3)

E84AVxxx3712

C 6

6

1

-

-

10

16

E84AVxxx5512

C 10

10

1.5

-

-

10

16

 30

3)

E84AVxxx7512

C 10

10

1.5

-

-

15

14

E84AVxxx1122

C16

16

2.5

-

-

20

12

 30

3)

E84AVxxx1522

C 20

20

4.0

-

-

25

10

E84AVxxx2222

C 25

25

6.0

-

-

30

10

1)

These values are recommendations only. Other dimensioning values/laying systems are possible (e.g. according to

VDE 0298-4).

The cable-cross sections apply under the following conditions: Use of PVC-insulated copper cables, conductor

temperature < 70 °C, ambient temperature < 45°C, no bundling of cables or cores, two loaded cores. Smaller cable

cross-sections are not permissible for technical reasons.

2)

Use UL-approved cable, fuses, and fuse holders only.

UL fuse: voltage  240 V, tripping characteristic for example ”H”, ”K5” or ”CC”.

The cable cross-sections apply under the following conditions: conductor temperature < 75 °C, ambient temperature

< 45°C. Smaller cable cross-sections are not permissible for technical reasons.

3)

Pulse-current sensitive or universal-current sensitive earth-leakage circuit breaker, short-time delay

If cables are longer than 50 m, the protective circuit-breaker may respond, depending on the cable type and

switching frequency.

Circuit breaker

Fuse of gG/gL utilisation category or semiconductor fuses of gRL utilisation category

Fuse

Observe national and regional regulations