Electrical installation

Common control terminals

Connection of relay output

6

220

EDS84ASC552 EN 9.1

Note!

ƒ

Switching of control signals:

– Use shielded cables

– HF-shield termination by PE connection

– The minimum load for a correct through-connection of the relay contacts

is 10 V DC and 10 mA. Both values must be exceeded at the same time.

ƒ

Use shielded cables for switching the control signals and establish the

HF-shield termination through a PE connection.

ƒ

For the switching operation of mains potentials, shielded cables are

sufficient.

ƒ

To protect the relay contacts, use a corresponding suppressor circuit in case

of an inductive or capacitive load!

ƒ

The service life of the relay depends on the load type (ohmic, inductive, or

capacitive) and the height of capacity to be switched.

Note!

The following notes are described in detail in the software manual ”Parameter

setting” in the section ”I/O terminals”, ”Relay output”:

ƒ

Use code C00118 to define the relay switching status.

ƒ

The minimum period for a valid HIGH or LOW signal to control the relay can

be defined via the codes C00423/3 and C00423/4.