Electrical installation

StateLine C control terminals

Digital inputs and outputs

6

227

EDS84ASC552 EN 9.1

Example circuit

E84AVSC...

24 V

int.

24E

DI1

DI2

DI3

DI4

RFR

DC 24 V
(+19.2 … +28.8 V)

S1

3.3k

3.3k

3.3k

3.3k

3.3k

X4

GND-IO

DO1

GIO

24I

GND-IO

E84AVSC...

24 V

int.

24E

DI1

DI2

DI3

DI4

RFR

S1

3.3k

3.3k

3.3k

3.3k

3.3k

X4

GND-IO

DO1

GIO

24I

GND-IO

8400SLC015

8400SLC016

DC 24 V

(+19.2 … +28.8 V)

E84AVSC...

24 V

int.

24E

DI1

DI2

DI3

DI4

RFR

S1

3.3k

3.3k

3.3k

3.3k

3.3k

X4

GND-IO

DO1

GIO

24I

GND-IO

DC 24 V
(+19.2 … +28.8 V)

S1

"

E84AVSC...

24 V

int.

24E

DI1

DI2

DI3

DI4

RFR

3.3k

3.3k

3.3k

3.3k

3.3k

X4

GND-IO

DO1

GIO

24I

GND-IO

8400SLC017

8400xLC022

Fig. 6-37

Wiring examples of the digital inputs and outputs

Wiring with one (or several) digital input (here: DI1), e.g. a PLC; optional: external

24 V supply

Digital control (relay, valve, ...) with internal 24 V supply

Digital control (relay, valve, ...) with external 24 V supply

Connection of an HTL incremental encoder with a maximum input frequency of

10 kHz

DI1

track A

DI2

track B

RFR

Input for controller enable; wiring is always required.

GIO

GND-IO

Ground reference potential for the digital inputs and outputs

X4

Terminal for the digital inputs and outputs