Technical data

Rated data

Operation at rated mains voltage 400 V

4

43

EDS84ASC552 EN 9.1

Switching frequency-dependent output currents

Output currents [A] at switching frequency

2 kHz

4 kHz

8 kHz

16 kHz

Type

I

arated2

I

aM2

I

arated4

I

aM4

I

arated8

I

aM8

I

arated16

I

aM16

E84AVxxx3714

1.3

2.6

1.3

2.6

1.3

2.6

0.9

2.1

E84AVxxx5514

1.8

3.6

1.8

3.6

1.8

3.6

1.2

3.0

E84AVxxx7514

2.4

4.8

2.4

4.8

2.4

4.8

1.6

4.0

E84AVxxx1124

3.2

6.4

3.2

6.4

3.2

6.4

2.1

5.3

E84AVxxx1524

3.9

7.8

3.9

7.8

3.9

7.8

2.6

6.4

E84AVxxx2224

5.6

11.2

5.6

11.2

5.6

11.2

3.7

9.2

E84AVxxx3024xxS

7.3

14.6

7.3

14.6

7.3

14.6

4.9

9.5

E84AVxxx3024xx0

7.3

14.6

7.3

14.6

7.3

14.6

4.9

9.5

E84AVxxx4024

9.5

19.0

9.5

19.0

9.5

17.1

6.3

9.5

E84AVxxx5524

13.0

26.0

13.0

26.0

13.0

19.5

8.7

11.7

E84AVxxx7524

16.5

33.0

16.5

33.0

16.5

26.4

11.0

16.5

E84AVxxx1134

23.5

47.0

23.5

47.0

23.5

32.9

15.7

21.2

E84AVxxx1534

32.0

64.0

32.0

57.1

32.0

43.2

21.3

27.2

E84AVxxx1834

40.0

78.0

40.0

78.0

40.0

72.2

27.0

48.8

E84AVxxx2234

47.0

89.3

47.0

89.3

47.0

75.2

31.3

49.4

E84AVxxx3034

61.0

112.1

61.0

89.3

61.0

75.2

41.0

53.1

E84AVxxx3734

76.0

136.8

76.0

115.2

76.0

97.2

51.0

72.0

E84AVxxx4534

89.0

169.1

89.0

146.9

89.0

120.2

60.0

84.6

I

aNx

Rated value of continuous output current

I

aMx

Maximum output current (overload current)

Periodic load change of 3 s with I

aMx

and recovery time of 12 s according to

the tables under chapter  4.4

Can be obtained in the setting ”x kHz fixed/...” in C00018

Switching

frequency

If the maximum heatsink temperature is reached, the switching frequency is

reduced to 4 kHz.
In the setting ”x kHz var./...” in C00018 the switching frequency is reduced

depending on the output current.
Depending on the switching frequency and e.g. the ambient temperature, it

may be required to reduce the output current (chapter 4.1, operating

conditions).

Advertising