Commissioning, Quick commissioning terminal control – Lenze 8400 User Manual

Page 248

Advertising
background image

Commissioning

Quick commissioning

Terminal control

7

248

EDS84ASC552 EN 9.1

Note!

The application ”actuating drive speed” is implemented with the Lenze

setting.

MCTRL: Act. speed val.

C00051

0 rpm

After attaching the keypad or

switching on the controller with

keypad attached, the connection

between keypad and controller is

established.

The connection has been established

when the code C00051 appears in

the display.

Then press the left function key.

SAVE

Par1 8400 StateLineC

User - Menu
Code list

Quick commissioning

SAVE

Par1 Quick commissioning

Terminals

Keypad

EDIT

Load Lenze setting

C00002/1

Starting from ”User menu” scroll down

with button to ”Quick commissioning”

menu

Click right button.

Select ”Keypad” menu.

Click right button.

Code 00002/1:

– Parameterise with left ”Edit”

function key

MCTRL: Act. speed val.

C00051

0 rpm

When the Lenze setting is loaded, the

display goes off for a short time.

When the display goes on again, the

main menu appears.

– The main menu settings can be

defined by the user using codes

C00465 ... C00469.

Press the left function key to go to the

user menu.

4. Enable controller:

– StateLine: Set terminal X4/RFR to HIGH potential (reference: X4/GIO).
– HighLine/TopLine: Set terminal X5/RFR to HIGH potential (reference: X5/GI).

5. Vary the motor speed with the potentiometer or by defining different fixed

setpoints:

DI2

DI1

Motor speed

0

0

Setpoint by potentiometer

0

1

40 % of C00011 (reference speed)

1

0

60 % of C00011 (reference speed)

1

1

80 % of C00011 (reference speed)

ƒ

Please observe
– the actual speed value: C00051
– the front LEDs ( 265)

6. Save the settings with  in the keypad.