Technical data

General data and operating conditions

4

29

EDS84ASC552 EN 9.1

Requirements on the motor cable
Capacitance per unit length

 2.5 mm

2

/AWG 14

C

Core/core

/C

Core/shield

< 75/150 pF/m

 4 mm

2

/AWG 12

C

Core/core

/C

Core/shield

< 150/300 pF/m

Electric strength

VDE 0250-1

U

0

/U

=

0.6/1.0 kV

(U

0

= r.m.s. value external - conductor/PE,

U = r.m.s. value - external conductor/external conductor)

UL

U  600 V

(U = r.m.s. value external conductor/external conductor)

Motor cable lengths without considering EMC limit values

Maximum motor cable length

1)

, (shielded)

U

rated

P

rated

after switching frequencies

[V]

[kW]

4 [kHz]

8 [kHz]

16 [kHz]

230

0.25 ... 2.2

50 m

50 m

50 m

400

0.37 ... 2.2

50 m

50 m

25 m

500

0.37 ... 2.2

50 m

25 m

15 m

2)

400/500

3 ... 15

50 m

50 m

50 m

400/500

18.5 ... 45

100 m

100 m

100 m

1)

If EMC conditions must be complied with, the permissible cable lengths may be shorter.

2)

At ambient temperatures of over 45 °C, only 13 m are permissible.

Motor cable lengths with interference suppression
Compliance with category C2 (industry), cable-guided

Motor cable length (shielded)

after interference suppression and required earth-leakage circuit breaker

U

rated

P

rated

Integrated

With SD filter

With LD filter

With LD and

sinusoidal filter

[V]

[kW]

30 mA FI 300 mA FI 30 mA FI

- FI

300 mA FI

- FI

- FI

230

0.25 ... 2.2

 25 m

-

25 m

25 - 50 m

25 - 50 m

-

50 - 100 m

400/500 0.37 ... 2.2

 25 m

-

25 m

1)

25 - 50 m

1)

25 - 50 m

1)

-

50 - 100 m

400/500 3.0 ... 15

-

 25 m

25 m

25 - 50 m

25 - 50 m

-

50 - 100 m

400/500 18.5 ... 45

-

 25 m

-

-

25 - 50 m

50 - 100 m

-

1)

Observe switching frequency-dependent restrictions according to table ”Motor cable lengths without considering EMC

limit values”

Device-dependent filter assignments: See chapter ”Accessories”, 11.3 and 11.4