Electrical installation, Example circuit – Lenze 8400 User Manual

Page 235

Advertising
background image

Electrical installation

HighLine C control terminals

Digital inputs and outputs

6

235

EDS84ASC552 EN 9.1

Example circuit

Note!

For stable digital output states, in particular during the starting phase of the

controller, you must use an external 24V supply for the digital outputs.

Note!

Digital inputs and digital outputs have separated reference potentials (GI and

GO). If you interconnect inputs and outputs, the reference potentials are

connected as well by an external bridge.

DC 24 V
(+19.2...+28.8 V)

S1

24 V int.

50

mA

24E

DI1

DI2

DI3

DI4

RFR

2.7k

2.7k

3.3k

3.3k

3.3k

X5

GND-I

DI5

DI6

DI7

GI

24I

1.6k

1.6k

3.3k

E84AVHC...

24O

DC 24 V
(+19.2...+28.8 V)

X4

DO1

DO2

DO3

GO

GND-O

E84AVHC...

8400HLC045

8400HLC045

24 V int.

50

mA

24E

DI1

DI2

DI3

DI4

RFR

DC 24 V
(+19.2...+28.8 V)

S1

3.3k

2.7k

2.7k

3.3k

X5

GND-I

DI5

DI6

DI7

GI

24I

3.3k

1.6k

1.6k

3.3k

"

E84AVHC...

8400xLC022

Fig. 6-44

Wiring examples of the digital inputs and outputs

Wiring with one (or several) digital input (here: DI1), e.g. a PLC; optional: external

24 V supply

Digital control (relay, valve, ...) with external 24 V supply

Connection of an HTL incremental encoder with a maximum input frequency of

200 kHz

DI1

track A

DI2

track B

X4

Terminal for the digital outputs

X5

Terminal for the digital inputs

GI

GND-I

Ground reference potential for the digital inputs

GO

GND-O

Ground reference potential for the digital outputs