Electrical installation – Lenze 8400 User Manual

Page 198

Advertising
background image

Electrical installation

Devices in the power range 0.37 ... 22 kW (3/PE AC 400 V)

Terminal assignment of the power connections

6

198

EDS84ASC552 EN 9.1

Connection of external brake resistor

Terminal X105

Labelling

Description

Rb1

Rb2

V

U

W

"

Rb1, Rb2

Brake resistor

Functional earth

HF-shield termination by connection to PE

8400GGXx002b

Terminal data

PE

Conductor

cross-section

Tightening

torque

Conductor

cross-section

Tightening

torque

[mm

2

]

[AWG]

[Nm]

[lb-in]

[mm

2

]

[AWG]

[Nm]

[lb-in]

E84AVxxx3714

E84AVxxx5514

E84AVxxx7514

E84AVxxx1124

E84AVxxx1524

E84AVxxx2224

E84AVxxx3024xxS

1 ... 2.5

18 ... 12

0.5

4.4

3.5 x 0.6

1 ... 6

18 ... 10

1.7

15

PZ 2

7 x 1

E84AVxxx3024xx0

E84AVxxx4024

E84AVxxx5524

1 ... 6

18 ... 10

0.5

4.4

3.5 x 0.6

2.5 ... 16

12 ... 6

3.4

30

PZ 2

7 x 1

E84AVxxx7524

E84AVxxx1134

E84AVxxx1534

1 ... 16

18 ... 6

1.2

10.6

5.5 x 1

2.5 ... 16

12 ... 6

3.4

30

PZ 2

7 x 1

E84AVxxx1834

E84AVxxx2234

1.5 ... 25

16 ... 2

3.5

31

6.5 x 1

2.5 ... 25

12 ... 2

4.0

35

PZ 2

7 x 1

Please read the information on how to install and connect the brake resistor in

the corresponding mounting instructions.

Advertising
This manual is related to the following products: