Introduction

8

259

EDS84ASC552 EN 9.1

Stop!

Requirements with regard to the brake cable (connection BD1/BD2):

ƒ

Brake cables must be shielded if they are incorporated in the motor cable.

– Operation with unshielded brake cables can destroy the motor brake

control.

– We recommend the use of Lenze system cables (motor cable with

separately shielded additional cores).

ƒ

In the case of a permanent magnet holding brake, observe the correct

polarity of the brake cable.

– If the terminals are inverted, the brake does not release. As the motor is

running against the closed brake, the brake can be destroyed.

ƒ

Apply the shield to PE on both sides.

Requirements with regard to the supply voltage U

DC

(connection +/-):

ƒ

Always supply the motor brake control with a separate 24 V supply.

– A common supply of the motor brake control and the controller control

card is not permissible, as otherwise the basic insulation between the two

components is reduced.

ƒ

Set U

DC

so that the operating voltage of the brake is within the permissible

range and the maximum supply voltage of the motor brake control is not

exceeded.

Cable length

0

0.5

1

1.5

2

2.5

3

3.5

4

4.5

5

I

Br

[A]

0

20

40

60

80

100

120

140

160

180

200

L

max

[m]

0.5 mm

2

(AWG 20)

0.75 mm

2

(AWG 18)

1 mm

2

(AWG 16)

U

DC

= 24 V DC

1.5 mm

2

(AWG 14)

2.5 mm

2

(AWG 12)

E94AZHY004

L

max

Maximum brake cable length in [m]

I

BR

Brake current in [A]

U

DC

Supply voltage of the motor brake control