Electrical installation

Common control terminals

System bus connection (CANopen)

6

216

EDS84ASC552 EN 9.1

6.6.2.2

Structure of the CAN network

Master

Slave 1

Slave n

X1

X1

X1

8400CAN006

Fig. 6-31

Wiring of system bus (CAN)

Bus cable length

Note!

ƒ

The permissible cable lengths must be observed.

ƒ

Please observe the reduction of the total cable length due to the signal delay

of the repeater, see example below ( 217).

ƒ

During mixed operation, multiple nodes are operated on one mains.

ƒ

If the respective total cable lengths of the nodes differ at the same baud

rate, the lower value must be used for the determination of the max. cable

length.

Total cable length
1. Check whether the total cable length is complied with.
The total cable lenth is determined by the baud rate:

Baud rate [kbps]

Max. bus length [m]

10 (not supported at the moment)

8075

20

4013

50

1575

125

600

250

275

500

113

800 (HighLine and TopLine,

StateLine from FW V11.0)

38

1000 (HighLine and TopLine,

StateLine from FW V11.0)

13

Tab. 6-1

Total cable length