Electrical installation

Installation according to EMC (installation of a CE-typical drive system)

Wiring outside of the control cabinet

6

174

EDS84ASC552 EN 9.1

Wiring on the mains side

ƒ

It is possible to connect the controller, mains choke or RFI filter to the mains via

single cores or unshielded cables.

ƒ

The cable cross-section must be rated for the assigned fuse protection (VDE 0160).

Wiring on the motor side

Stop!

The motor cable is highly susceptible to interference. Therefore you will

achieve an optimum wiring on the motor side if you

ƒ

exclusively use shielded and low-capacitance motor cables.

ƒ

do not integrate any further cable into the motor cable (e.g. for blowers

etc.).

ƒ

shield the supply cable for temperature monitoring of the motor (PTC or

thermostat) and install it separately from the motor cable.

Special conditions allow you to integrate the supply cable for temperature monitoring of

the motor into the motor cable: ( 169)