Electrical installation

Devices in the power range 0.25 ... 2.2 kW (1/N/PE AC 230 V)

Terminal assignment of the power connections

6

182

EDS84ASC552 EN 9.1

Connecting the controller to protective earth
Using the PE connection on the motor side the controller and the motor cable can be

connected to protective earth. Additional protective earthing of the controller can be

carried out via this connection in order to comply with the requirements regarding the

operation of devices with an increased discharge current to PE.
How to proceed:
1. Observe the above-mentioned steps regarding stripping and shielding.
2. Connect a second cable to the PE connection and earth it. ( 176).

8400GG039

Fig. 6-13

Connection of controllers with device sizes 1 ... 3 to protective earth

Mains connection

Terminal X100

Labelling

Description

PE

L1

Mains phase L

n

Neutral conductor

PE

PE conductor on the supply side

8400GG1001b

Terminal data

PE

Conductor

cross-section

Tightening

torque

Conductor

cross-section

Tightening

torque

[mm

2

]

[AWG]

[Nm]

[lb-in]

[mm

2

]

[AWG]

[Nm]

[lb-in]

E84AVxxx2512

E84AVxxx3712

E84AVxxx5512

E84AVxxx7512

1 ... 2.5

18 ... 12

0.5

4.4

3.5 x 0.6

1 ... 6

18 ... 10

1.7

15

PZ 2

7 x 1

E84AVxxx1122

E84AVxxx1522

E84AVxxx2222

1 ... 6

18 ... 10

0.5

4.4

3.5 x 0.6

1 ... 6

18 ... 10

1.7

15

PZ 2

7 x 1