Electrical installation

Devices in a power range of 30 ... 45 kW (3/PE AC 400 V)

Terminal assignment of the power connections

6

202

EDS84ASC552 EN 9.1

Connecting the controller to protective earth
Using the PE connection on the motor side the controller and the motor cable can be

connected to protective earth. Additional protective earthing of the controller can be

carried out via this connection in order to comply with the requirements regarding the

operation of devices with an increased discharge current to PE.
How to proceed:
1. Observe the above-mentioned steps regarding stripping and shielding.
2. Connect a second cable to the PE connection and earth it. ( 199).

8400GG094a

Fig. 6-23

Controller connection of device size GG7 to protective earth

Mains connection

Terminal X100

Labelling

Description

L1

L2

L3

Connection of the mains phases L1, L2, L3

PE

Connection for the PE conductor

8400GG096a

Terminal data

PE

Conductor

cross-section

Tightening

torque

Conductor

cross-section

Tightening

torque

[mm

2

]

[AWG]

[Nm]

[lb-in]

[mm

2

]

[AWG]

[Nm]

[lb-in]

E84AVxxx3034

E84AVxxx3734

E84AVxxx4534

16 ... 50

6 ... 0

4.0

35

Inbus

SW 4

2.5 ... 25

12 ... 2

4.0

35

PZ 2

7 x 1