Technical data, Rated data operation at rated mains voltage 400 v, 725 v, adjustable – Lenze 8400 User Manual

Page 44: Made possible through the resistor r, Used

Advertising
background image

Technical data

Rated data

Operation at rated mains voltage 400 V

4

44

EDS84ASC552 EN 9.1

Rated data for internal brake chopper
Switching threshold V

BRmax

: 725 V, adjustable

R

Bmin

[]

I

BRmax

[A]

P

BRmax

[kW]

I

BRd

[A]

P

Bd

[kW]

t

Z

[s]

t

on

[s]

t

fp

[s]

Type
E84AVxxx3714

390

1.9

1.3

1.9

1.3

-

-

E84AVxxx5514

390

1.9

1.3

1.9

1.3

-

-

E84AVxxx7514

390

1.9

1.3

1.9

1.3

-

-

E84AVxxx1124

180

4.0

2.9

4.0

2.9

-

-

E84AVxxx1524

180

4.0

2.9

4.0

2.9

-

-

E84AVxxx2224

150

4.8

3.5

4.8

3.5

-

-

E84AVxxx3024xxS

82

8.8

6.4

8.8

6.4

-

-

E84AVxxx3024xx0

82

8.8

6.4

8.8

6.4

-

-

E84AVxxx4024

47

15.4

11.2

13.0

9.4

-

-

E84AVxxx5524

47

15.4

11.2

13.0

9.4

-

-

E84AVxxx7524

27

26.9

19.5

26.9

19.5

-

-

E84AVxxx1134

27

26.9

19.5

26.9

19.5

-

-

E84AVxxx1534

18

40.3

29.2

40.3

29.2

-

-

E84AVxxx1834

15

48.3

35.0

48.3

35.0

-

-

E84AVxxx2234

15

48.3

35.0

48.3

35.0

-

-

E84AVxxx3034

7.5

96.7

70.1

96.7

70.1

-

-

E84AVxxx3734

7.5

96.7

70.1

96.7

70.1

-

-

E84AVxxx4534

7.5

96.7

70.1

96.7

70.1

-

-

R

Bmin

Minimum brake resistance, nominal value ±10 %

I

BRmax

Peak current

P

BRmax

Peak braking power

I

BRd

Continuous current RMS - important for the dimensioning of the cables

P

Bd

Continuous braking power

t

Z

Cycle time, periodic load change with running time and recovery time

t

on

Running time

t

Z

- t

on

Recovery time

t

fp

Maximum running time without initial load and compliance with the recovery

time

Note on brake chopper operation according to cUL/CSA
Brake chopper operation according to cUL/CSA is ensured if the running time t

on

is not

higher than 30% compared to the cycle time t

z

.

The condition is fulfilled if the continuous braking power P

d

is not higher than 30%

compared to the peak braking power P*

BRmax

made possible through the resistor R

B

used:

t

on

t

z

≤ 0.3 ;

P

d

P

:

BRmax

≤ 0.3 ;

P

:

BRmax

=

U

BRmax

2

R

B

R

B

Brake resistor used (nameplate data)

V

BRmax

Switching threshold of the inverter (725 V at V

LN

= 400 V, 790 V at V

Lr

= 500 V)

VLr

Rated mains voltage

P*

BRmax

Peak braking power of the resistor used

P

d

Continuous braking power of the load to be braked (dependent on the

application)

t

on

Running time

t

Z

Cycle time (”duty cycle”)