Electrical installation
Devices in a power range of 30 ... 45 kW (3/PE AC 400 V)
Terminal assignment of the power connections
6
200
EDS84ASC552 EN 9.1
6.5.2
Terminal assignment of the power connections
Preparing the cable installation
To connect the shield of the motor cable, use the shield lug of the rear shield sheet. Position
the shield sheet as follows:
1. Release the holding screw of the shield sheet.
2. Bring the shield sheet into the lock-in position.
3. Tighten the holding screw to lock the shield sheet.
8400GG093
Fig. 6-22
Locate shield sheet in position