17

Working with the FB Editor

17.4

Reconfiguring the predefined interconnection

1142

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

How to change the processing order manually:

1. Use the list field at the top right to change from the Editor to the overview.

• The overview displays all function blocks of the interconnection in the order of their

processing

• In the first "Order" column the order index of each function block is listed.

2. Unless already selected, select the entry "Manual selection" in the Optimisation... list field.

3. Select the function block which is to receive a different position within the processing

order.

• If you click further function blocks while pressing <Ctrl> they are added to an already

existing selection (multi-selection).

• The <Shift> key serves to select a related area of function blocks.

4. Move the function block(s) to the desired position using the

and

buttons.

• The

button serves to exchange two selected function blocks with regard to their

order.

5. Repeat steps 3 and 4 until the required processing order has been established.

Changing the processing order according to an automatically generated selection
In addition to the manual selection, the Optimisation... list field also offers two options for an

automatic adaptation of the processing order:

Signal flow: The processing order is optimised according to the signal flow.
Topology: The processing order is optimised according to the x/y arrangement of the function

blocks in the FB Editor.

As long as an automatic adaptation has been selected, a manual change of the processing order is

not possible.