Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

87

3

Commissioning

3.10

PC manual control

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

How to activate PC manual control:

1. If an online connection to the controller has not been established yet:

Go online.

2. Select the Application parameters tab from the Workspace.
3. Go to the Overview dialog level and click the PC manual control button.

• The following safety note is displayed first:

• Click the Cancel button to abort the action and close the dialog box.
• The Timeout monitoring input field serves to adapt the timeout for monitoring the

connection between the PC and the controller.

4. To acknowledge the note and activate PC manual control:

Click the Connect PC manual control button.

• The controller is inhibited via device command (

C00002/16

).

• The PC manual control operator dialog is displayed.

Note!

For activated PC manual control:
The online connection between the PC and the controller is monitored by the controller.

• If the online connection is interrupted for longer than the set timeout (Lenze setting:

2 s):

• Error response "Fault" is triggered, i.e. the motor becomes torqueless and is

coasting unless it already is at standstill.

• The "

Ck16: Time overflow manual control

" error message is entered into the

logbook.

PC manual control provides the Motion Control Kernel and the motor interface with all

required control signals and setpoint signals.

• The existing application (function block interconnection) is now decoupled from

these interfaces but will be processed as before and remains unchanged.

• It does not matter what type of motor control is set in

C00006

.