C00118 | digoutx: inversion, C00120 | setting of motor overload (i·xt), C00122 | initial value motor overload (i·xt) – Lenze 8400 User Manual

Page 767: C00120, R load setting, C00122, C00118, 16 parameter reference

Advertising
background image

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

767

16

Parameter reference

16.2

Parameter list | C00118

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00118

C00120

C00122

Parameter | Name:

C00118 | DigOutX: Inversion

Data type: UNSIGNED_8

Index: 24457

d

= 5F89

h

The polarity of each digital output of the device can be inverted via this bit field.

Digital terminals

Setting range

(min. hex value | max. hex value)

Lenze setting

0x00

0xFF 0x00 (decimal: 0)

Value is bit-coded: (= bit set)

Info

Bit 0  Reserved
Bit 1  DO1 inverted

Inversion of digital output 1

Bit 2  DO2 inverted

Inversion of digital output 2

Bit 3  Reserved
Bit 4  Reserved
Bit 5  Reserved
Bit 6  Reserved
Bit 7  Reserved

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Parameter | Name:

C00120 | Setting of motor overload (I²xt)

Data type: INTEGER_16

Index: 24455

d

= 5F87

h

Operating threshold for the "OC6: Motor overload (I²xt)" error message

• The response for reaching the threshold can be selected in

C00606

.

• The current thermal motor load is displayed in

C00066

.

Motor overload monitoring (I2xt)

Setting range

(min. value | unit | max. value)

Lenze setting

0.00

%

250.00 100.00 %

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00122 | Initial value motor overload (I²xt)

Data type: UNSIGNED_16

Index: 24453

d

= 5F85

h

From version 07.00.00

The thermal motor load displayed in

C00066

is pre-initialised with the value set here when the device is connected

to the mains.

• If "100.00 %" is set, the last value at switching off the device is used for the initialisation.

• Recommended setting for operation according to UL: 50.00 %

Motor overload monitoring (I2xt)

Setting range

(min. value | unit | max. value)

0.00

%

100.00

Subcodes

Lenze setting

Info

C00122/1

0.00 %

Initial value motor overload (I²xt)

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Advertising