Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

129

5

Motor control (MCTRL)

5.1

Motor selection/Motor data

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Stop!

Motors with electronic nameplates (ETS) must not be operated on 8400 controllers!

Note!

Sensorless vector control in particular requires the motor data parameters to be set. The

motor data comprise the data of the motor nameplate and the data of the motor

equivalent circuit.
If the motor has been selected via the motor catalogue of the »Engineer« or the motor

data have been adapted offline using the »Engineer«, all motor data must then be

copied to the controller and saved power-failure-proof to the memory module (device

command:

C00002/11

) when an online connection has been established.

Note!

Setting a rated motor frequency with a decimal position
If the motor has a rated motor frequency with a decimal position (e.g. motor nameplate

data "23.7 Hz"):

Up to and including version 06.xx.xx

, the following motor nameplate data must be

increased by a factor of 10:

C00089

: Rated motor frequency

(a value of "23.7 Hz", for instance, must be increased to 237 Hz.)

C00081

: Rated motor power

C00087

: Rated motor speed

C00090

: Rated motor voltage

From version 12.00.00,

the rated motor frequency must be entered without decimal

position to clearly identify the right motor type. (a value of "23.7 Hz", for instance,

must be set to 23 Hz in

C00089

)

C01000

displays the set motor type (ASM or PSM).

C00969

displays the set number of motor pole pairs.