C00107 | dc braking: hold time, C00114 | diginx: inversion, C00107 – Lenze 8400 User Manual

Page 765: C00114, Fter the hold time, Inputs in, 16 parameter reference

Advertising
background image

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

765

16

Parameter reference

16.2

Parameter list | C00107

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00107

C00114

Parameter | Name:

C00107 | DC braking: Hold time

Data type: UNSIGNED_32

Index: 24468

d

= 5F94

h

Maximum hold time of the manual DC injection brake

• A time can be set here after which the DC injection brake is switched off automatically to prevent the motor from

thermal overload.

DC-injection braking

Setting range

(min. value | unit | max. value)

Lenze setting

0.000

s

999.000 999.000 s

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1000

Parameter | Name:

C00114 | DigInX: Inversion

Data type: UNSIGNED_16

Index: 24461

d

= 5F8D

h

The polarity of each digital input of the device can be inverted via this bit field.

Digital terminals

Setting range

(min. hex value | max. hex value)

Lenze setting

0x0000

0xFFFF 0x0000 (decimal: 0)

Value is bit-coded: (= bit set)

Info

Bit 0  Invert. DI1

Inversion of digital input 1

Bit 1  Invert. DI2

Inversion of digital input 2

Bit 2  Invert. DI3

Inversion of digital input 3

Bit 3  Invert. DI4

Inversion of digital input 4

Bit 4  Invert. DI5

Inversion of digital input 5

Bit 5  Invert. DI6

Inversion of digital input 6

Bit 6  Reserved
Bit 7  Reserved
Bit 8  Reserved
Bit 9  Reserved

Bit 10  Reserved
Bit 11  Reserved
Bit 12  Reserved
Bit 13  Reserved
Bit 14  Reserved
Bit 15  Invert CInh

Inversion of digital input RFR (controller enable)

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT