5.4

V/f characteristic control (VFCplus)

In case of the V/f characteristic control (VFCplus), the motor voltage of the inverter is determined by

means of a linear or quadratic characteristic depending on the field frequency or motor speed to be

generated. The voltage follows a preselected characteristic.

Stop!

• The following must be observed when operating drives with quadratic V/f

characteristic:

• Please always check whether the corresponding drive is suitable for operation with

a quadratic V/f characteristic!

• If your pump drive or fan drive is not suitable for operation with a quadratic V/f

characteristic, you must either use the V/f characteristic control function with a

linear V/f characteristic or the sensorless vector control (SLVC).

• For adjustment, observe the thermal performance of the connected asynchronous

motor at low output frequencies.

• Usually, standard asynchronous motors with insulation class B can be operated for

a short time with their rated current in the frequency range 0 Hz ... 25 Hz.

• Contact the motor manufacturer to get the exact setting values for the max.

permissible motor current of self-ventilated motors in the lower speed range.

• If you select the quadratic V/f characteristic, we recommend to set a lower V

min

.

• The nameplate data of the motor (at least rated speed and rated frequency) must be

entered if, instead of a standard motor, an asynchronous motor is used with the

following values:

• rated frequency ≠ 50 Hz (star) or
• rated frequency ≠ 87 Hz (delta) or
• number of pole pairs ≠ 2

Note!

When the auto DCB threshold (

C00019

) is set > 0 rpm, there is no torque at the motor

shaft in the lower speed range!

Automatic DC-injection braking (Auto-DCB)

( 249)