2 basic settings, Basic settings, 5motor control (mctrl) – Lenze 8400 User Manual
Page 151
Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05
151
5
Motor control (MCTRL)
5.4
V/f characteristic control (VFCplus)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.4.2
Basic settings
The "Initial commissioning steps" listed in the table below are sufficient for a simple characteristic
control.
• Detailed information on the individual steps can be found in the following subchapters.
Tip!
Information on the optimisation of the control mode and the adaptation to the real
application is provided in chapter "
Parameterisable additional functions are described correspondingly in the chapter
"
Parameterisable additional functions
Initial commissioning steps
1.
Defining the V/f characteristic shape
2.
Defining current limits (Imax controller)