Configuration dialog, L-force | plc designer – Lenze PLC Designer PLC Designer (R3-1) User Manual

Page 775

Advertising
background image

L-force | PLC Designer

General Editors

DMS 4.1 EN 03/2011 TD29

773

Configuration dialog
When inserting a task ('Add Object' command) in the Task Configuration in the Devices
view, the Task Editor dialog for setting the task properties will be opened:

Abb. 423 Configuration dialog for a task

Insert the desired attributes:

Note: The task name can be modified by editing the respective entry in the devices
tree.

Priority (0-31): (a number between 0 and 31; 0 is the highest priority, 31 is the lowest),
Type: The selection list offers the following task types:
Cyclic: The task will be processed cyclic according to the time definition given in the
field 'Interval' (see below).
Freewheeling: The task will be processed as soon as the program is started and at the
end of one run will be automatically restarted in a continuous loop. There is no cycle
time defined.
Status: The task will be started if the variable defined in the Event field is true.
Event: The task will be started as soon as the variable defined in the Event field gets a
rising edge.

Advertising